Installation Instructions
The Modbus com interface need the libmodbus library to work. Follow the steps below to set up your environment before compiling 4diacĀ FORTE.
-
libmodbus files should be placed in the following folder structure:
-
[ibmodbushome]/include/modbus: include files -
[libmodbushome]/lib:libmodbus.lib(windows) orlibmodbus.so(posix)
-
-
When configuring 4diacĀ FORTE project with CMake choose
[ibmodbushome]asFORTE_COM_MODBUS_LIB_DIR -
forte.exemust be able to find the dynamic libmodbus library after build. Therefore copylibmodbus.dll/soto folder withforte.exeor addlibmodbus.dll/soto library include path.
Parameters
Modbus Client (TCP)
Usage of the Modbus Client (TCP):
modbus[(protocol:)ip:port:pollFreqency:functionCode:(slaveId):readAddresses:sendAddresses(:responseTimeout:byteTimeout)]
-
protocol: tcp (tcp is default)
-
ip: address of Modbus server, e.g. 127.0.0.1
-
port: preferably above 1024, default is 502
-
pollFrequency: polling frequency in milliseconds
-
functionCode: an integer between 1 and 4
-
1 = Read Coils
-
2 = Read Discrete Inputs
-
3 = Read Holding Registers
-
4 = Read Input Register
-
-
slaveId (optional): the slave id used by the modbus server (0xFF is standard); this is in principle an optional parameter but some modbus devices (e.g. Siemens SENTRON PAC power measurement devices) need this parameter in order to establish a connection
-
readAddresses: addresses can be specified between 0-65535 more than one address (max 100) can be specified using
-
comma for separate addresses 0,2,65500
-
dots for interval 5..10
-
combination 0,5..10,2,65500
-
-
sendAddresses: addresses can be specified between 0-65535 if data is only read sendAddresses should be left empty more than one address (max 100) can be specified using
-
comma for separate addresses 0,2,65500
-
dots for interval 5..10
-
combination 0,5..10,2,65500
-
-
responseTimeout (optional): timeout in milliseconds to wait for a response (500ms is default)
-
byteTimeout (optional): timeout in milliseconds between two consecutive bytes (500ms is default)
Example:
modbus[127.0.0.1:502:2000:3:1:0..3]
Modbus Client (RTU)
Usage of the Modbus Client (RTU):
modbus[protocol:device:baudRate:parity:dataBit:stopBit:pollFreqency:functionCode(slaveId):readAddresses:sendAddresses(:responseTimeout:byteTimeout)]
Parameter meaning:
-
protocol: rtu
-
device: serial device, e.g., /dev/ttyS0
-
baudRate: baud rate
-
parity: N for none, E for even, O for odd
-
dataBit: number of data bits
-
stopBit: number of stop bits
-
pollFrequency: polling frequency in milliseconds
-
functionCode: an integer between 1 and 4, whereas
-
1 = Read Coils
-
2 = Read Discrete Inputs
-
3 = Read Holding Registers
-
4 = Read Input Register
-
-
slaveId (optional): the slave id used by the modbus server (0xFF is standard); this is in principle an optional parameter but some modbus devices (e.g. Siemens SENTRON PAC power measurement devices) need this parameter in order to establish a connection
-
readAddresses: addresses can be specified between 0-65535. More than one address (max 100) can be specified using
-
comma for separate addresses 0,2,65500
-
dots for interval 5..10
-
combination 0,5..10,2,65500
-
-
sendAddresses: addresses can be specified between 0-65535. More than one address (max 100) can be specified using
-
comma for separate addresses 0,2,65500
-
dots for interval 5..10
-
combination 0,5..10,2,65500
-
-
responseTimeout (optional): timeout in milliseconds to wait for a response (500ms is default)
-
*byteTimeout# (optional): timeout in milliseconds between two consecutive bytes (500ms is default)
Example:
modbus[rtu:/dev/ttyS0:19200:E:8:1:2000:3:247:6142,6132,6137:64025..64025,63995..63995]